RCC columns: short or long, minimum eccentricity and axial capacity

How IS 456 classifies columns, the minimum eccentricity rule, and the formula for the axial load capacity of a short column.

Columns carry load from beams and slabs down to the foundation. IS 456 handles them in two ways depending on how slender they are.

Short or long?

lexD < 12 and leyb < 12 → short column

Otherwise the column is slender (long) and must also be designed for the additional moments caused by its own deflection.

Effective length depends on end restraint (IS 456 Table 28), from 0.65 l for both ends fully fixed up to 2 l for a cantilever column.

Minimum eccentricity

Real columns are never loaded perfectly through their centre. IS 456 requires every column to be designed for at least

emin = l500 + D30, but not less than 20 mm

Axial capacity of a short column

When emin does not exceed 0.05 D, the axial load capacity is:

Pu = 0.4 fck Ac + 0.67 fy Asc

Ac is the net concrete area (Ag − Asc) and Asc the longitudinal steel area. The factors 0.4 and 0.67 already include the material safety factors and the effect of minimum eccentricity.

Worked example

A 400 × 400 mm short column with 8 bars of 20 mm. M25 concrete, Fe 500 steel.

Asc = 8 × 314 = 2513 mm², Ac = 160000 − 2513 = 157487 mm².

Pu = 0.4 × 25 × 157487 + 0.67 × 500 × 2513 = 2417 kN

Detailing rules

Item Rule
Longitudinal steel 0.8% to 6% of Ag (4% is a practical limit)
Minimum bars 4 in a rectangular column, 6 in a circular one
Minimum bar size 12 mm
Tie diameter at least ¼ of the largest bar and not less than 6 mm
Tie pitch least of: least lateral dimension, 16 × smallest bar diameter, 300 mm
Cover at least 40 mm, or the bar diameter if larger

Quick check

A braced column 400 mm × 400 mm has an effective length of 4.4 m. It is: