Do each test step by step, exactly as the IS code lays it out. Press each action, take the readings, work out the result yourself, and finish with a data sheet, observation sheet and final report you can print.

  1. Set up
  2. Normal consistency
  3. Initial setting
  4. Final setting
  5. Report

Step 1 of 11 · Set up

Check the lab conditions

📘 IS 4031 (Part 4) cl. 4; IS 4031 (Part 1)

Cement tests are done at 27 ± 2 °C and 65 ± 5 % relative humidity. Check both before you start, and keep the cement, water and apparatus at room temperature.

Lab conditionsRoom temperature— °CRelative humidity— %01020304050mm above platedistance from bottom—Vicat mould on glass plate (IS 5513)

Data sheet

TestNormal consistency, initial and final setting time of cement
CodesIS 4031 (Part 4):1988 consistency, IS 4031 (Part 5):1988 setting time, apparatus IS 5513, limits IS 269:2015
CementOPC 43 grade (sample)
ApparatusVicat apparatus with plunger (10 mm dia), needle (1 mm²) and annular attachment; mould 40 mm deep; balance; gauging trowel; stop watch
Lab conditions27 ± 2 °C, relative humidity 65 % (required 65 ± 5 %)
Cement per trial400 g

Observation sheet: normal consistency

IS 4031 (Part 4). Cement 400 g per trial.

TrialWater %Water (g)Plunger stop from bottom (mm)
125100·
227108·
329116·
431124·
P =5 to 7 mm

Observation sheet: initial setting

IS 4031 (Part 5). Water 0.85 P = ….

Time from adding water (min)Needle stop from bottom (mm)
120·
130·
140·
150·
160·
170·

Observation sheet: final setting

Time (min)Annular ring marks surface?
180·
210·
225·
240·

Sample values are simulated for learning. Real tests must be done on the actual sample with calibrated apparatus.